Gas Control Panel-four Channel Sound And Light Alarm Gas Monitor Control Panel
The product has high stability. With high accuracy and high intelligence, the external control port is rich, and the user can freely choose the type of the connected transmitter and the access port.
INTRODUCTION
This product is a single-channel / dual-channel / four-way (4-20) mA / RS485 transmitter signal input intelligent control system developed by the company. The product has high stability. High accuracy and high intelligence, the external control port is rich, the user can freely choose the type of the connected transmitter and the access port, and can perform on-site detection and alarm by simple setting. The system has integrated sound and light alarms and provides a relay normally open control terminal.
The system is widely used in applications where toxic and harmful gases need to be detected. When the index of a certain gas to be tested in the field exceeds or falls below the set standard, the system will perform a series of alarm actions, such as alarm, exhaust, tripping, etc.
Detection principle: Collect standard 4~20mA signal input or RS485 communication input (optional), analyze and display the current gas concentration of each channel, and operate related alarm signals, and transmit the information to the computer through RS485 bus.
Applicable objects: The system supports input signals of various standard detectors, such as gas detectors: carbon monoxide, hydrogen sulfide, sulfur dioxide, hydrogen, ammonia, oxygen, chlorine and combustible gases.
Product type |
BH-50 Gas controller |
Channel |
Single channel,two channels,four channels |
Power supply |
AC220V±10% 50Hz |
Consumption |
≦10W |
Signal input |
4~20mA and RS485 |
Single output |
two lines RS485(MODBUS) |
Working temperature |
-10℃~50℃ |
Working humidity |
0-95%RH (no dew) |
Contact output |
Free contact output, max power 1kW |
Installation method |
Wall-mounted |
Dimensions |
380x210x80mm(L×W×H) |
SPECIFICATIONS
Measurable Gas Meter |
gas |
Range |
Detection Accuracy |
90% Response Time |
Minimun Readout |
Alarm Set Point Low/High |
PH3 |
0-2000ppm |
±5%(F.S) |
≦25s |
0.01ppm |
0.3/5ppm |
O2 |
0-30%vol |
±5%(F.S) |
≦15s |
0.10% |
19.5%/23.0% |
EX |
0-100%LEL |
±5%(F.S) |
≦5s |
1%LEL |
25.0%/50.0%LEL |
CO |
0-1000ppm |
±5%(F.S) |
≦25s |
1ppm |
50ppm/100ppm |
CO2 |
0-5000ppm |
±5%(F.S) |
≦25s |
1ppm |
1000ppm/2000ppm |
H2S |
0-100ppm |
±5%(F.S) |
≦30s |
1ppm |
10ppm/20ppm |
NO2 |
0-20ppm |
±5%(F.S) |
≦25s |
0.1ppm |
3ppm/10ppm |
NO |
0-250ppm |
±5%(F.S) |
≦60s |
1ppm |
25ppm/50ppm |
SO2 |
0-100ppm |
±5%(F.S) |
≦30s |
0.1ppm |
2ppm/10pppm |
CL2 |
0-20ppm |
±5%(F.S) |
≦30s |
0.1ppm |
1ppm/10ppm |
NH3 |
0-100ppm |
±5%(F.S) |
≦50s |
1ppm |
25ppm/50ppm |
H2 |
0-1000ppm |
±5%(F.S) |
≦60s |
1ppm |
50ppm/10ppm |
HCN |
0-50ppm |
±5%(F.S) |
≦200s |
0.1ppm |
10ppm/20ppm |
HCL |
0-20ppm |
±5%(F.S) |
≦60s |
0.1ppm |
5ppm/10ppm |
CH4 |
0-100%LEL |
±5%(F.S) |
≦5s |
1%LEL |
25.0%/50.0%LEL |
Note: Not all gases are listed, if the gas you need is not listed, please contact us.