Fixed concentration Gas Detector BH-60 With Display alarm detector Gas Monitor
BH-60 fixed gas detector adopts advanced catalytic gas sensor or electrochemical sensor, which can translate the gas concentration in the air to the digital signal output. The detector working with gas controller can be used to detect gas in refinery, chemical plant, LPG station, boiler room, painting plant and other places with gas exists.
INTRODUCTION
Product type
|
BH-60 fixed gas detector/transmitter
|
Explosion proof grade
|
Exd ⅡC T6 Gb
|
Response time
|
≦30S
|
Power supply
|
DC24V±10%
|
Working temperature
|
-20℃~50℃
|
Output current
|
4-20mA
|
Working humidity
|
0-95%RH
|
Contact output
|
Free contact output, max power 1kW
|
Single input
|
4~20mA and RS485
|
Installation method
|
Wall-mounted
|
Shell material
|
Aluminum
|
Dimensions
|
190x150x95mm(L×W×H)
|
SPECIFICATIONS
Model
|
Range
|
L-alarm
|
H-alarm
|
CO
|
0-1000ppm
|
35ppm
|
200ppm
|
O2
|
0-30%vol
|
19.5%vol
|
23.5%vol
|
H2
|
0-100%LEL
|
20%LEL
|
50%LEL
|
H2S
|
0-100ppm
|
10ppm
|
20ppm
|
CH4
|
0-100%LEL
|
20%LEL
|
50%LEL
|
C2H4O
|
0-20ppm
|
10ppm
|
15ppm
|
C2H4
|
0-100%LEL
|
20%LEL
|
50%LEL
|
C3H8
|
0-100%LEL
|
20%LEL
|
50%LEL
|
C2H5OH
|
0-100%LEL
|
20%LEL
|
50%LEL
|
NH3
|
0-100ppm
|
25ppm
|
50ppm
|
CL2
|
0-20ppm
|
5ppm
|
10ppm
|
O3
|
0-20ppm
|
5ppm
|
10ppm
|
SO2
|
0-20ppm
|
2ppm
|
5ppm
|
PH3
|
0-20ppm
|
0.3ppm
|
5ppm
|
CO2
|
0-50000ppm
|
1000ppm
|
2000ppm
|
NO
|
0-250ppm
|
20ppm
|
50ppm
|
NO2
|
0-20ppm
|
5ppm
|
10ppm
|
HCN
|
0-500ppm
|
10ppm
|
20ppm
|
HCL
|
0-50ppm
|
10ppm
|
20ppm
|
CH2O
|
0-10ppm
|
2ppm
|
5ppm
|
VOC
|
0-100ppm
|
20ppm
|
50ppm
|
C6H6
|
0-100ppm
|
20ppm
|
50ppm
|