Gas Control Panel-four Channel Sound And Light Alarm Gas Monitor Control Panel

Gas Control Panel-four Channel Sound And Light Alarm Gas Monitor Control Panel

Model No.︰BH-50

Brand Name︰AERMANDA

Country of Origin︰China

Unit Price︰US $ 152 / Piece

Minimum Order︰1 Piece

Inquire Now

Product Description

Gas Control Panel-four Channel Sound And Light Alarm Gas Monitor Control Panel

The product has high stability. With high accuracy and high intelligence, the external control port is rich, and the user can freely choose the type of the connected transmitter and the access port.

 

INTRODUCTION

This product is a single-channel / dual-channel / four-way (4-20) mA / RS485 transmitter signal input intelligent control system developed by the company. The product has high stability. High accuracy and high intelligence, the external control port is rich, the user can freely choose the type of the connected transmitter and the access port, and can perform on-site detection and alarm by simple setting. The system has integrated sound and light alarms and provides a relay normally open control terminal.

The system is widely used in applications where toxic and harmful gases need to be detected. When the index of a certain gas to be tested in the field exceeds or falls below the set standard, the system will perform a series of alarm actions, such as alarm, exhaust, tripping, etc.

Detection principle: Collect standard 4~20mA signal input or RS485 communication input (optional), analyze and display the current gas concentration of each channel, and operate related alarm signals, and transmit the information to the computer through RS485 bus.

Applicable objects: The system supports input signals of various standard detectors, such as gas detectors: carbon monoxide, hydrogen sulfide, sulfur dioxide, hydrogen, ammonia, oxygen, chlorine and combustible gases.

 

Product type                                                             BH-50 Gas controller
Channel Single channel,two channels,four channels
Power supply AC220V±10% 50Hz
Consumption ≦10W
Signal input 4~20mA and RS485
Single output two lines RS485(MODBUS)
Working temperature -10℃~50℃
Working humidity 0-95%RH (no dew)
Contact output Free contact output, max power 1kW
Installation method Wall-mounted
Dimensions 380x210x80mm(L×W×H)

 

SPECIFICATIONS

Measurable Gas Meter
gas  Range Detection Accuracy 90% Response Time Minimun Readout Alarm Set Point Low/High
PH3 0-2000ppm ±5%(F.S) ≦25s 0.01ppm 0.3/5ppm
O2 0-30%vol ±5%(F.S) ≦15s 0.10% 19.5%/23.0%
EX 0-100%LEL ±5%(F.S) ≦5s 1%LEL 25.0%/50.0%LEL
CO 0-1000ppm ±5%(F.S) ≦25s 1ppm 50ppm/100ppm
CO2 0-5000ppm ±5%(F.S) ≦25s 1ppm 1000ppm/2000ppm
H2S 0-100ppm ±5%(F.S) ≦30s 1ppm 10ppm/20ppm
NO2 0-20ppm ±5%(F.S) ≦25s 0.1ppm 3ppm/10ppm
NO 0-250ppm ±5%(F.S) ≦60s 1ppm 25ppm/50ppm
SO2 0-100ppm ±5%(F.S) ≦30s 0.1ppm 2ppm/10pppm
CL2 0-20ppm ±5%(F.S) ≦30s 0.1ppm 1ppm/10ppm
NH3 0-100ppm ±5%(F.S) ≦50s 1ppm 25ppm/50ppm
H2 0-1000ppm ±5%(F.S) ≦60s 1ppm 50ppm/10ppm
HCN 0-50ppm ±5%(F.S) ≦200s 0.1ppm 10ppm/20ppm
HCL 0-20ppm ±5%(F.S) ≦60s 0.1ppm 5ppm/10ppm
CH4 0-100%LEL ±5%(F.S) ≦5s 1%LEL 25.0%/50.0%LEL

Note: Not all gases are listed, if the gas you need is not listed, please contact us.